Product description
Boiler Super Series 4
Ideal Commercial Heating`s Super range is proven to deliver exceptional high efficiency commercial and industrial heating performance. The Super Series 4 range consists of the Super Series 4 comprising identical 50kW modules with outputs from 50kW to 600kW, with the number of modules in use dependent on the maximum load. Fitted on slide rails, the modules are located in an insulated stainless steel boiler casing. The products of combustion first give up their heat to water flowing through the modules then are discharged.
The heat exchanger consists of extruded copper finned tubes in a circular arrangement around the gas burner. Copper tubes are expanded into cast iron headers, onto which cast iron cover plates are bolted.
Suitable for vertical or horizontal assembly, Super range installations can save over 30% of the typical plant room space normally used by conventional boilers.
Super efficient, straightforward to specify, easy to install and service. Ideal`s Super range is the proven performer in high efficiency modular boiler systems.
Low weight and quiet operation make the boiler Super Series 4 ideal for the placement in the attic, where in the neighbouring rooms can be placed offices and accomodation. For examples of succesfull instalations of this type please contact our team.
Efficiency |
Features
|
Specification
Super Series 4 (50–300)
Model | 50/V | 100/V | 150/V | 150/VA | 200/V | 250/V | 250/H | 300/V | 300/H | |
---|---|---|---|---|---|---|---|---|---|---|
Modules | 1 | 2 | 3 | 3 | 4 | 5 | 5 | 6 | 6 | |
Output | kW | 50 | 100 | 150 | 150 | 200 | 250 | 250 | 300 | 300 |
Height | mm | 782 | 1432 | 1912 | 1487 | 1487 | 1967 | 1443 | 1972 | 1443 |
Width | mm | 439 | 701 | 701 | 1171 | 1171 | 1171 | 1783 | 1171 | 1783 |
Depth | mm | 698 | ||||||||
Flow/Return Connections |
DN flange | 40 | 50 | 65 | 65 | 65 | 80 | 80 | 80 | 80 |
Gas Inlet | BSP | RC¾ | RC1 | RC1¼ | RC1¼ | RC1¼ | RC1½ | RC1½ | RC1½ | RC1½ |
Flue Size | mm | 125 | 175 | 200 | 200 | 250 | 250 | 250 | 300 | 300 |
Maximum Working Pressure |
bar | 6 | ||||||||
Water Content |
L | 4.5 | 11.9 | 20.7 | 21.7 | 26.2 | 37.7 | 39.7 | 44.5 | 44.5 |
Dry Weight (Approx) |
kg | 82.1 | 187.7 | 274.1 | 296.4 | 348 | 461 | 411.2 | 511.2 | 513.7 |
Boiler Clearances (mm) |
Front | 950 | ||||||||
Back | 25 | |||||||||
Left | 450 | 900 | ||||||||
Right | 450 | 900 | ||||||||
Seasonal Efficiency (Ref L2) |
% | 84.50 | 84.39 | 84.75 | 84.76 | 84.96 | 84.96 | 84.96 | 84.96 | 84.96 |
Super Series 4 (350–600)
Model | 350/V | 400/V | 400/H | 450/V | 500/V | 500/H | 550/V | 550/H | 600/V | 600/H | |
---|---|---|---|---|---|---|---|---|---|---|---|
Modules | 1 | 2 | 3 | 3 | 4 | 5 | 5 | 6 | 12 | 12 | |
Output | kW | 50 | 100 | 150 | 150 | 200 | 250 | 250 | 300 | 600 | 600 |
Height | mm | 782 | 1432 | 1912 | 1487 | 1487 | 1967 | 1443 | 1972 | 2144 | 2144 |
Width | mm | 439 | 701 | 701 | 1171 | 1171 | 1171 | 1783 | 1171 | 1833 | 1833 |
Depth | mm | 1350 | |||||||||
Flow/Return Connections |
DN flange | 40 | 50 | 65 | 65 | 65 | 80 | 80 | 80 | 125 | 125 |
Gas Inlet | BSP | RC2 | RC2 | RC2 | RC2 | RC2 | RC2 | RC2 | RC2 | RC2 | RC2 |
Flue Size | mm | 125 | 175 | 200 | 200 | 250 | 250 | 250 | 300 | 450 | 450 |
Maximum Working Pressure |
bar | 6 | |||||||||
Water Content |
L | 4.5 | 11.9 | 20.7 | 21.7 | 26.2 | 37.7 | 39.7 | 112 | 112 | 112 |
Dry Weight (Approx) |
kg | 82.1 | 187.7 | 274.1 | 296.4 | 348 | 461 | 411.2 | 1129 | 1129 | 1129 |
Boiler Clearances (mm) |
Front | 950 | |||||||||
Back | 950 | ||||||||||
Left | 450 | 1200 | |||||||||
Right | 450 | 1200 | |||||||||
Seasonal Efficiency (Ref L2) |